Private customers can also find our range in our partner store Ampha-Analyse.
Sulfite (SO₃²-) is used in water treatment as an oxygen binding agent to prevent corrosion
in steam boilers, heating systems and closed cooling systems. As a reducing agent
, Sulfite reacts with dissolved oxygen and thus protects pipelines and system components from
oxygen corrosion.
The optimum Sulfite concentration in boiler water is 20-30 mg/l SO₃²-.
Regular monitoring is essential, as values that are too low do not provide sufficient corrosion protection
, while concentrations that are too high are uneconomical and promote the formation of Sulfite.
Sulfite is also used as a preservative and antioxidant in the food industry.
Monitoring the concentration of sulfite is therefore of great importance in various industrial sectors.
The CALDUR® Sulfite Test Set – Colorimetric is based on the proven thiobenzoic acid method.
After adding two reagents to the water sample, a
characteristic color develops within 3 minutes, the intensity of which is proportional to the Sulfite concentration.
The measured value is determined by direct color comparison with a supplied 6-level color chart.
Optionally, the sample can also be evaluated photometrically with the WINLAB Data Line photometer.
Ideal for regular checks in boiler systems – immediate results on site
Covers the entire practical range for boiler water and industrial applications
Cost-efficient for daily checks in power plants, heating systems and industrial operations
Flexible for simple on-site tests or precise laboratory analyses with photometer
No additional technology required – ideal for quick routine checks
Safe transportation and protection of reagents – durable and reliable even under harsh conditions
For best results, the water sample should be clear and free of suspended solids.
If the water is cloudy, pre-filtration with a filter paper (e.g. Whatman No. 1) is recommended.
The measurement should be carried out as soon as possible after sampling, as Sulfite oxidizes in the air.
| Measuring level | Description |
|---|---|
| 0.5 mg/l | Very low concentration (light yellow) |
| 1.0 mg/l | Low concentration (yellow) |
| 2.5 mg/l | Increased concentration (yellow-orange) |
| 5.0 mg/l | Average concentration (orange) |
| 10 mg/l | High concentration (orange-brown) |
| 20 mg/l | Very high concentration (brown) |
You can carry out 150 measurements with one CALDUR® Sulfite test kit.
This refers to the quantity of reagents contained.
Readability: ± 1 color level
Reproducibility: Very good if the application instructions are followed
Interferences: Turbidity and coloration of the sample can influence the result (filter the sample if necessary). High concentrations of sulphide can interfere with the measurement.
| Dilution | Procedure | Calculation of the measured value |
|---|---|---|
| 1:1 | 5 ml sample + 5 ml distilled water | Measured value × 2 |
| 1:4 | 2 ml sample + 8 ml distilled water | Measured value × 5 |
| 1:9 | 1 ml sample + 9 ml distilled water | Measured value × 10 |
The measured value is below the detection limit. This indicates that the Sulfite concentration is very low. For boiler water, this means insufficient corrosion protection – the addition of sulphite should be increased.
| Property | Value |
|---|---|
| Parameters | Sulfite (SO₃²-) |
| Item number | 31-072530 |
| Method | Colorimetric |
| Measuring principle | Color comparison with 6-stage color chart (thiobenzoic acid method) |
| Measuring range | 0.5 to 20 mg/l SO₃²- |
| Color scale | 6 measuring levels (0.5 / 1.0 / 2.5 / 5.0 / 10 / 20 mg/l) |
| Analysis time | 3 minutes |
| Number of provisions | 150 |
| Packaging | Hinged lid box |
| Packaging size | 103 x 91 x 36 mm |
| weight | approx. 150 g |
| Component | Component description |
|---|---|
| 2 reagent bottles | Reagent A and B with detailed labeling |
| 1 test tube | With 10 ml scale |
| 1 color chart | With 6 measuring levels for precise color comparison |
| Operating instructions | Detailed in DE/EN |
| Safety data sheets | For all reagents |
| Packaging | Robust hinged lid box (103 x 91 x 36 mm) |
| Reagent | Volume | Shelf life | Notes |
|---|---|---|---|
| Reagent A (Sulfite) | 30 ml | 36 months (36M) | Shake before use, store in a cool, dark place |
| Reagent B (Sulfite) | 10 ml | 36 months (36M) | Shake before use |
Shelf life: The shelf life starts from the date of manufacture (printed on the bottle).
After opening, the reagents should be used within 18 months.
Store the test kit in a dry, cool place (10-25°C) and away from direct sunlight.
| Packaging | Hinged lid box, Refill pack |
|---|