Reagent for CALDUR® Silicate – Photometric:
See also:
CALDUR® Silicate Test Set – Photometric
What is silicate measured for?
Silicate (SiO₂) is a naturally occurring water constituent that comes from the dissolution of rocks and minerals. Silicate is particularly critical in boiler water technology, as it can form glass-like deposits (silicate scale) at high temperatures and pressures, which are extremely difficult to remove.
In high-pressure boilers, the silicate content must be kept particularly low, as even low concentrations can lead to deposits on turbine blades. Typical limit values are 0.02-0.5 mg/l SiO₂ depending on the operating pressure.
Silicate control is also important in drinking water treatment and in the production of ultrapure water (e.g. for the semiconductor industry).
How does the test set work?
The CALDUR® Silicate Test Set – Photometric is based on the molybdate method. After adding three reagents to the water sample, a yellow silicomolybdate complex is formed within 8 minutes, the concentration of which is precisely determined using the WINLAB Data Line photometer.
Advantages of the CALDUR® test set
Wide measuring range 0.1 – 30 mg/l SiO₂
Covers the range from boiler water to raw water
100 provisions per set
Economical for regular checks
High precision due to photometric evaluation
Objective, reproducible measurement results with the WINLAB Data Line
Proven molybdate method
Specific for dissolved silicate
Areas of application
Pond / lake
Groundwater / well water
Drinking / tap water
Aquaristics
Pool / Swimming pool
Industrial processing
Boiler water
Food preparation
Waste water treatment
Carrying out the measurement:
Fill the round cuvette with sample up to the 10 ml mark
Add 5 drops of reagent A and mix
Add 3 drops of reagent B and mix
Add 5 drops of reagent C and mix
Wait for 8 minutes reaction time
Insert the cuvette into the WINLAB Data Line photometer
Start measurement – result is displayed directly in mg/l SiO₂
Tip for best results
Samples must be collected in plastic vessels – glass releases silicate and falsifies the measurement. Allow boiler water samples to cool down to room temperature before measuring.
Important notes
Do not use glass jars – only plastic!
Adhere exactly to the response time of 8 minutes
Allow sample to cool to room temperature before measuring
Wipe the cuvette with a lint-free cloth before measuring
Phosphate in high concentrations can influence the result
Requires WINLAB Data Line photometer (Art. 37-000100)
Measuring range
Property
Value
Measuring range
0.1 to 30 mg/l SiO₂
Resolution
0.1 mg/l
Method
Molybdate method, photometric evaluation
Advantage of photometric measurement:
In contrast to the colorimetric method (color chart), the photometer provides exact numerical values with a higher resolution. Intermediate values are calculated automatically – ideal for documentation and quality assurance.
Number of possible destinations
You can carry out 100 measurements with one CALDUR® Silicate Photometric Test Set.
This refers to the quantity of reagents contained.
Recommended limit values
Application
Recommended silicate content
Low pressure boiler (< 20 bar)
< 5 mg/l SiO₂
Medium pressure vessel (20-60 bar)
< 1 mg/l SiO₂
High pressure boiler (> 60 bar)
< 0.5 mg/l SiO₂
Feed water
< 0.02 mg/l SiO₂
Note:
Silicate deposits are particularly dangerous as they can hardly be removed using conventional cleaning methods. Regular inspection is therefore essential.
What to do if measured values are out of range?
Measured value > 30 mg/l
Verduction
Execution
Calculation of the measured value
1:1
5 ml sample + 5 ml silicate-free water
Measured value × 2
Measured value < 0.1 mg/l
Measured value is below the detection limit. For more sensitive measurements, please contact our technical support.
Specifications at a glance
Property
Value
Parameters
Silicate (SiO₂)
Item number
31-073522
Method
Photometric (molybdate)
Measuring principle
Photometric evaluation with WINLAB Data Line
Measuring range
0.1 to 30 mg/l SiO₂
Resolution
0.1 mg/l
Duration of analysis
8 minutes
Number of provisions
100
Number of reagents
3
Packaging
Plastic bag
Scope of delivery
3 reagent bottles (reagent A, reagent B, reagent C) with detailed labeling
1 round cuvette (10 ml)
Detailed operating instructions (DE/EN)
Safety data sheets for all reagents
Resealable plastic bag
Reagent details
Reagent
Volume
Shelf life
Notes
Reagent A (molybdate)
30 ml
24 months (24M)
Molybdate reagent, shake before use
Reagent B (acid)
10 ml
24 months (24M)
Acid reagent, dose carefully
Reagent C (reducing agent)
10 ml
24 months (24M)
Shake before use
Shelf life: The shelf life starts from the date of manufacture (printed on the bottle).
After opening, the reagents should be used within 12 months.
Store the test kit in a dry, cool place (10-25°C) and protected from direct sunlight.
Required accessories
For the photometric measurement you need a WINLAB Data Line photometer with the appropriate method for silicate.
The photometer is not included in the test set and is available separately.